• en

срочный займ онлайн на карту оформить

Specifications

This unit is meant for professional use only. It is an aid in detecting unshielded, live wires and dangerous AC potentials. It is not a substitute for voltage measuring devices. Treat all wires as if they are voltage carrying. The unit will not detect DC voltages or AC voltages when conductors are fully enclosed and shielded as in a grounded metal conduit or solid metal enclosures.

HotStick AC Voltage Detector Specifications

    • Sensitivity, externally switchable:
      • 3 settings
    • Detection Range:
      • The detection range or sensitivity is defined as the distance between the HotStick AC Voltage Detector and the wire conductor with the HotStick positioned for maximum indication. Signal “detection ” shall be defined as a beeping rate of at least one indication every 2 seconds.
    • Typical Detection Distance in meters /(feet ):
         Mode Switch Setting
      VoltageFrequencySetupHigh SensitivityLow SensitivityFocused Setting
      120 VAC
      220 VAC
      60 Hz
      50 Hz
      Single conductor
      (6′ above ground)
      4.6m
      (15′)
      0.9m
      (3′)
      150mm
      (0.5′)
      120 VAC
      220 VAC
      60 Hz
      50 Hz
      Conductor laying on wet soil0.9m
      (3′)
      150mm
      (0.5′)
      25mm
      (0.1′ )
      7.2 kV
      16 kV
      60 Hz
      50 Hz
      Overhead distribution line
      (single insulator)
      65m
      (210′)
      21m
      (70′)
      6m
      (20′)
      46 kV60 HzOverhead transmission line
      (several insulators)
      >150m
      (>500′)
      >60m
      (>200′)
      >20m
      (>70′)
    • Signal Indication
      • Audible (beep) and visual (LED)
      • Beep rate will increase (or decrease)
    • Frequency Range
      • C Voltages 20 Hz to 100 Hz
    • Self-Test
      • Built-in, 3-second self-test after turn-on.
    • Insulation:
      • PVC plastic housing. (Note: Direct contact with high tension wires should be avoided)
    • Safety:
      • Designed for intrinsically safe operation
    • Batteries:
      • 4× AA alkaline batteries, NEDA 15A, Duracell MN1500 or equivalent
    • Battery Life:
      • Continuous use: 300 hours, typical use: 1 year
    • Battery Check:
      • Built-in low voltage warning
    • Battery Change:
      • Requires removal of lanyard
    • Water Resistance:
      • Splashwater-proof
    • Temperature Range:
      • Operating:
        • -30 to +50°C (-22 to +122°F)
      • Storage & transport:
        • −40 to +70°C (−40 to +158°F)
    • Size:
      • 45 mm (1 3⁄4′′ ) diameter × 521 mm (20 1⁄2″) long
    • Weight, including batteries:
      • 570 grams (1 lb. 4 oz.)
    • Shipping weight:
      • 910 grams (2 lbs.)

The tool has found many applications especially with first responders, fire, police and ambulances responding to vehicular accidents; with search and rescue operations in urban and rural settings as well as with cleanup crews working on downed trees after wind and ice storms. But also industrial user and anybody else who may unknowingly be exposed to the dangers of electrical shock or electrocution will appreciate the AC Hot Stick.